We have radiant heat (all copper tubing) in our floor. We have a leak in the system. Can your product be used to repair it? Also would your product affect the transmission of heat in the floor.

-Ryan

Ryan, epoxy lining technology is great for protecting a new system and can assist with repairing an older system with one or more small diameter leaks less than 1/8” in size. It’s not the cure all for all pipe leaks: the pipe must be metal; it must be structurally sound; and the leak must be from a pinhole, and not a crack, split or some other catastrophic failure. If the leak is too large, a repair must be made prior to the lining procedure. A certified CuraFlo professional can work with your system’s installer to determine the best way to make the repair(s).

Once in the pipes, the epoxy lining does provide some insulating properties (i.e. it will slow down the heat transfer), but this is not significant enough to interfere with the performance of your radiant heating system. The circulating hot water temperature of in-floor radiant heating systems are typically between 120° to 125° Fahrenheit (48.9° – 51.7° Celsius). Most epoxies are effective at these temperatures, and will allow your system to perform as designed.

-Brian

Posted by Brian on Monday, January 21st, 2008